Power Systems on the FE Electrical and Computer exam

Power Systems accounts for 9 of the 110 questions — 8.2% of your exam. It is one of the three heaviest areas on this paper, so it is worth your study time before almost anything else.

Questions9
Share of exam8.2%
Rank by weight3/17
In our bank29

What Power Systems covers

On the FE Electrical and Computer exam this area covers single and three-phase power, real, reactive and apparent power, power factor and correction, transformers, transmission lines, per-unit analysis, and fault and protection basics.

What the questions look like: A power factor correction, a three-phase power computation, or a transformer turns-ratio problem.

Worth knowing cold: Keep the power triangle at hand and be careful with line versus phase quantities; that distinction causes most errors here.

3 free Power Systems practice problems

These come from our FE Electrical and Computer bank, written to the same specification as the exam. Try each one before opening the solution.

Problem 1

A three-phase, $60.0\text{ Hz}$, $480\text{ V}_{rms}$ (line-to-line) industrial facility serves an aggregate balanced three-phase inductive load of $S_1 = 150.0\text{ kVA}$ operating at a lagging power factor of $PF_1 = 0.750$. To avoid electric utility low power factor penalty surcharges, a delta-connected three-phase capacitor bank is installed in parallel with the load to improve the overall power factor to $PF_2 = 0.950$ lagging, as represented in the complex power triangle diagram. What is the required capacitance per phase $C$ of the delta-connected capacitor bank, in microfarads (μF)?

  1. A79.6 μF
  2. B125 μF
  3. C180 μF
  4. D239 μFcorrect
Show the solution

**Step 1: Calculate Real and Reactive Power of the Initial Load** From the FE Reference Handbook (Power Systems / Power Factor Correction): $$P = S_1 \cdot PF_1 = (150.0\text{ kVA})(0.750) = 112.50\text{ kW}$$ $$\theta_1 = \arccos(0.750) = 41.41^\circ$$ $$Q_1 = P \cdot \tan(\theta_1) = 112.50 \times \tan(41.41^\circ) = 112.50 \times 0.8819 = 99.215\text{ kVAR}$$ **Step 2: Determine Required Reactive Power at Corrected Power Factor** For $PF_2 = 0.950$ lagging: $$\theta_2 = \arccos(0.950) = 18.195^\circ$$ $$Q_2 = P \cdot \tan(\theta_2) = 112.50 \times \tan(18.195^\circ) = 112.50 \times 0.32868 = 36.977\text{ kVAR}$$ **Step 3: Calculate Required Three-Phase Capacitive Compensation (Q_C)** $$Q_{C(total)} = Q_1 - Q_2 = 99.215 - 36.977 = 62.238\text{ kVAR}$$ For a balanced three-phase delta bank, reactive power per phase is: $$Q_{C(phase)} = \frac{Q_{C(total)}}{3} = \frac{62.238\text{ kVAR}}{3} = 20.746\text{ kVAR} = 20{,}746\text{ VAR}$$ **Step 4: Compute Capacitance C per Branch for Delta Connection** In a delta connection, the voltage across each capacitor is the full line-to-line voltage: $$V_C = V_{LL} = 480\text{ V}_{rms}$$ Reactive power formula for capacitor: $$Q_{C(phase)} = \frac{V_C^2}{X_C} = \omega C V_{LL}^2$$ $$C = \frac{Q_{C(phase)}}{\omega \cdot V_{LL}^2}$$ Given $\omega = 2\pi f = 2\pi(60) = 376.99\text{ rad/s}$: $$C = \frac{20{,}746\text{ VAR}}{(376.99\text{ rad/s}) \times (480\text{ V})^2} = \frac{20{,}746}{376.99 \times 230{,}400} = \frac{20{,}746}{86{,}858{,}496}$$ $$C = 2.3885 \times 10^{-4}\text{ F} = 238.85\ \mu\text{F} \approx 239\ \mu\text{F}$$ Conclusion: The required capacitance per phase in delta is **239 μF**. Distractor Analysis: - Option A: Assumes star (wye) connection instead of delta, dividing required capacitance by 3. - Option B: Calculates based on total three-phase reactive power without dividing per phase. - Option C: Uses phase-to-neutral voltage instead of line-to-line voltage across the delta branch. - Option D: Correct. Uses delta line-to-line voltage V_LL = 480 V and per-phase reactive power Q_C = 20.75 kVAR.

Problem 2

A three-phase, $460\text{ V}$ (line-to-line), $60\text{ Hz}$, 4-pole, Y-connected induction motor has the following per-phase equivalent circuit parameters referred to the stator: - Stator resistance: $R_1 = 0.250\ \Omega$, Stator leakage reactance: $X_1 = 0.500\ \Omega$ - Magnetizing reactance: $X_m = 30.0\ \Omega$ - Rotor resistance referred to stator: $R_2' = 0.200\ \Omega$ - Rotor leakage reactance referred to stator: $X_2' = 0.400\ \Omega$ Using the Thévenin equivalent circuit of the stator seen by the rotor, at what rotor mechanical speed $n$ does the maximum (pull-out / breakdown) internal torque occur?

  1. A1,620 rpm (at breakdown slip s = 0.100)
  2. B1,414 rpm (at breakdown slip s = 0.215)correct
  3. C1,250 rpm (at breakdown slip s = 0.306)
  4. D1,080 rpm (at breakdown slip s = 0.400)
Show the solution

**Step 1: Calculate Synchronous Speed and Line-to-Neutral Voltage** From the FE Reference Handbook (Power Systems / Induction Machines): For $f = 60\text{ Hz}$ and $p = 4$ poles: $$n_{sync} = \frac{120 f}{p} = \frac{120(60)}{4} = 1{,}800\text{ rpm}$$ Line-to-neutral terminal voltage: $$V_1 = \frac{V_{LL}}{\sqrt{3}} = \frac{460}{\sqrt{3}} = 265.58\text{ V}$$ **Step 2: Determine Thévenin Equivalent Parameters of the Stator** Thévenin impedance looking back into the stator terminals from the air-gap: $$Z_{TH} = R_{TH} + j X_{TH} = j X_m \parallel (R_1 + j X_1) = \frac{j30.0(0.250 + j0.500)}{0.250 + j30.50}$$ $$R_{TH} \approx R_1 \left(\frac{X_m}{X_1 + X_m}\right)^2 = 0.250 \left(\frac{30.0}{30.5}\right)^2 = 0.250 (0.9675) = 0.2419\ \Omega$$ $$X_{TH} \approx X_1 = 0.500\ \Omega$$ **Step 3: Calculate Slip at Maximum (Breakdown) Torque** From the maximum power transfer condition applied to the rotor resistance branch $R_2'/s$: $$s_{max} = \frac{R_2'}{\sqrt{R_{TH}^2 + (X_{TH} + X_2')^2}} = \frac{0.200}{\sqrt{(0.2419)^2 + (0.500 + 0.400)^2}}$$ $$s_{max} = \frac{0.200}{\sqrt{0.0585 + 0.8100}} = \frac{0.200}{\sqrt{0.8685}} = \frac{0.200}{0.9319} = 0.2146 \approx 0.215$$ **Step 4: Compute Rotor Mechanical Speed at Breakdown** $$n = n_{sync}(1 - s_{max}) = 1{,}800(1 - 0.2146) = 1{,}800(0.7854) = 1{,}413.7\text{ rpm} \approx 1{,}414\text{ rpm}$$ Conclusion: Maximum pull-out torque occurs at a rotor speed of **1,414 rpm**. Distractor Analysis: - Option A: at breakdown slip s = 0.100 - Option B: at breakdown slip s = 0.215 (Correct) - Option C: at breakdown slip s = 0.306 - Option D: at breakdown slip s = 0.400

Problem 3

A three-phase electrical power network is modeled on a common base of $100.0\text{ MVA}$ and $115.0\text{ kV}$ in the transmission section: - Synchronous generator subtransient reactance: $X_d'' = 0.15\text{ pu}$ - Step-up power transformer leakage reactance: $X_T = 0.10\text{ pu}$ - Transmission line series reactance: $X_{line} = 0.15\text{ pu}$ A bolted three-phase symmetrical fault occurs at the remote receiving-end bus of the transmission line. Prefault voltage is nominal ($V_f = 1.00\text{ pu}$). What are the per-unit subtransient symmetrical fault current $I_f''$ and the corresponding three-phase short-circuit capacity $S_{sc}$?

  1. A1.25 pu (with S_sc = 125.0 MVA)
  2. B1.67 pu (with S_sc = 167.0 MVA)
  3. C2.50 pu (yielding short-circuit capacity S_sc = 250.0 MVA and I_f = 1.26 kA)correct
  4. D3.33 pu (with S_sc = 333.0 MVA)
Show the solution

**Step 1: Compute Total Thevenin Subtransient Reactance $X_{th}''$** From the FE Reference Handbook (Power Systems / Fault Analysis / Symmetrical Three-Phase Faults): Because all reactances are connected in series between the internal generator EMF and the fault location on a common base: $$X_{th}'' = X_d'' + X_T + X_{line} = 0.15\text{ pu} + 0.10\text{ pu} + 0.15\text{ pu} = 0.40\text{ pu}$$ **Step 2: Calculate Subtransient Fault Current $I_f''$ in Per Unit** $$I_f'' = \frac{V_f}{X_{th}''} = \frac{1.00\text{ pu}}{0.40\text{ pu}} = 2.50\text{ pu}$$ **Step 3: Calculate Short-Circuit Capacity $S_{sc}$** $$S_{sc} = \frac{S_{base}}{X_{th}''} = \frac{100.0\text{ MVA}}{0.40} = 250.0\text{ MVA}$$ **Step 4: Verify Base Current and Physical Current** $$I_{base} = \frac{S_{base}}{\sqrt{3} V_{base}} = \frac{100.0 \times 10^6\text{ VA}}{\sqrt{3}(115.0 \times 10^3\text{ V})} = 502.04\text{ A}$$ $$I_{f,actual}'' = 2.50 \times 502.04\text{ A} = 1{,}255.1\text{ A} = 1.255\text{ kA} \approx 1.26\text{ kA}$$ Conclusion: The fault current is **$2.50\text{ pu}$** yielding a short-circuit capacity of **$250.0\text{ MVA}$**. Distractor Analysis: - Option A: with S_sc = 125.0 MVA - Option B: with S_sc = 167.0 MVA - Option C: yielding short-circuit capacity S_sc = 250.0 MVA and I_f = 1.26 kA (Correct) - Option D: with S_sc = 333.0 MVA

Find out where you actually stand

A free 20-question diagnostic across every FE Electrical and Computer knowledge area, scored in the real exam interface. You get a projected score and the areas costing you the most — so you know whether Power Systems is where your time should go at all.

Start the free Electrical & Computer diagnostic

Retaking the FE Electrical and Computer exam?

Copy the scores from your NCEES diagnostic report and see whether Power Systems is where your next attempt gains the most points, or whether another area deserves the time first.

Analyze my diagnostic report

Other FE Electrical and Computer knowledge areas