Problem 1
A three-phase, $60.0\text{ Hz}$, $480\text{ V}_{rms}$ (line-to-line) industrial facility serves an aggregate balanced three-phase inductive load of $S_1 = 150.0\text{ kVA}$ operating at a lagging power factor of $PF_1 = 0.750$. To avoid electric utility low power factor penalty surcharges, a delta-connected three-phase capacitor bank is installed in parallel with the load to improve the overall power factor to $PF_2 = 0.950$ lagging, as represented in the complex power triangle diagram. What is the required capacitance per phase $C$ of the delta-connected capacitor bank, in microfarads (μF)?
- A79.6 μF
- B125 μF
- C180 μF
- D239 μFcorrect
Show the solution
**Step 1: Calculate Real and Reactive Power of the Initial Load** From the FE Reference Handbook (Power Systems / Power Factor Correction): $$P = S_1 \cdot PF_1 = (150.0\text{ kVA})(0.750) = 112.50\text{ kW}$$ $$\theta_1 = \arccos(0.750) = 41.41^\circ$$ $$Q_1 = P \cdot \tan(\theta_1) = 112.50 \times \tan(41.41^\circ) = 112.50 \times 0.8819 = 99.215\text{ kVAR}$$ **Step 2: Determine Required Reactive Power at Corrected Power Factor** For $PF_2 = 0.950$ lagging: $$\theta_2 = \arccos(0.950) = 18.195^\circ$$ $$Q_2 = P \cdot \tan(\theta_2) = 112.50 \times \tan(18.195^\circ) = 112.50 \times 0.32868 = 36.977\text{ kVAR}$$ **Step 3: Calculate Required Three-Phase Capacitive Compensation (Q_C)** $$Q_{C(total)} = Q_1 - Q_2 = 99.215 - 36.977 = 62.238\text{ kVAR}$$ For a balanced three-phase delta bank, reactive power per phase is: $$Q_{C(phase)} = \frac{Q_{C(total)}}{3} = \frac{62.238\text{ kVAR}}{3} = 20.746\text{ kVAR} = 20{,}746\text{ VAR}$$ **Step 4: Compute Capacitance C per Branch for Delta Connection** In a delta connection, the voltage across each capacitor is the full line-to-line voltage: $$V_C = V_{LL} = 480\text{ V}_{rms}$$ Reactive power formula for capacitor: $$Q_{C(phase)} = \frac{V_C^2}{X_C} = \omega C V_{LL}^2$$ $$C = \frac{Q_{C(phase)}}{\omega \cdot V_{LL}^2}$$ Given $\omega = 2\pi f = 2\pi(60) = 376.99\text{ rad/s}$: $$C = \frac{20{,}746\text{ VAR}}{(376.99\text{ rad/s}) \times (480\text{ V})^2} = \frac{20{,}746}{376.99 \times 230{,}400} = \frac{20{,}746}{86{,}858{,}496}$$ $$C = 2.3885 \times 10^{-4}\text{ F} = 238.85\ \mu\text{F} \approx 239\ \mu\text{F}$$ Conclusion: The required capacitance per phase in delta is **239 μF**. Distractor Analysis: - Option A: Assumes star (wye) connection instead of delta, dividing required capacitance by 3. - Option B: Calculates based on total three-phase reactive power without dividing per phase. - Option C: Uses phase-to-neutral voltage instead of line-to-line voltage across the delta branch. - Option D: Correct. Uses delta line-to-line voltage V_LL = 480 V and per-phase reactive power Q_C = 20.75 kVAR.
Problem 2
A three-phase, $460\text{ V}$ (line-to-line), $60\text{ Hz}$, 4-pole, Y-connected induction motor has the following per-phase equivalent circuit parameters referred to the stator: - Stator resistance: $R_1 = 0.250\ \Omega$, Stator leakage reactance: $X_1 = 0.500\ \Omega$ - Magnetizing reactance: $X_m = 30.0\ \Omega$ - Rotor resistance referred to stator: $R_2' = 0.200\ \Omega$ - Rotor leakage reactance referred to stator: $X_2' = 0.400\ \Omega$ Using the Thévenin equivalent circuit of the stator seen by the rotor, at what rotor mechanical speed $n$ does the maximum (pull-out / breakdown) internal torque occur?
- A1,620 rpm (at breakdown slip s = 0.100)
- B1,414 rpm (at breakdown slip s = 0.215)correct
- C1,250 rpm (at breakdown slip s = 0.306)
- D1,080 rpm (at breakdown slip s = 0.400)
Show the solution
**Step 1: Calculate Synchronous Speed and Line-to-Neutral Voltage** From the FE Reference Handbook (Power Systems / Induction Machines): For $f = 60\text{ Hz}$ and $p = 4$ poles: $$n_{sync} = \frac{120 f}{p} = \frac{120(60)}{4} = 1{,}800\text{ rpm}$$ Line-to-neutral terminal voltage: $$V_1 = \frac{V_{LL}}{\sqrt{3}} = \frac{460}{\sqrt{3}} = 265.58\text{ V}$$ **Step 2: Determine Thévenin Equivalent Parameters of the Stator** Thévenin impedance looking back into the stator terminals from the air-gap: $$Z_{TH} = R_{TH} + j X_{TH} = j X_m \parallel (R_1 + j X_1) = \frac{j30.0(0.250 + j0.500)}{0.250 + j30.50}$$ $$R_{TH} \approx R_1 \left(\frac{X_m}{X_1 + X_m}\right)^2 = 0.250 \left(\frac{30.0}{30.5}\right)^2 = 0.250 (0.9675) = 0.2419\ \Omega$$ $$X_{TH} \approx X_1 = 0.500\ \Omega$$ **Step 3: Calculate Slip at Maximum (Breakdown) Torque** From the maximum power transfer condition applied to the rotor resistance branch $R_2'/s$: $$s_{max} = \frac{R_2'}{\sqrt{R_{TH}^2 + (X_{TH} + X_2')^2}} = \frac{0.200}{\sqrt{(0.2419)^2 + (0.500 + 0.400)^2}}$$ $$s_{max} = \frac{0.200}{\sqrt{0.0585 + 0.8100}} = \frac{0.200}{\sqrt{0.8685}} = \frac{0.200}{0.9319} = 0.2146 \approx 0.215$$ **Step 4: Compute Rotor Mechanical Speed at Breakdown** $$n = n_{sync}(1 - s_{max}) = 1{,}800(1 - 0.2146) = 1{,}800(0.7854) = 1{,}413.7\text{ rpm} \approx 1{,}414\text{ rpm}$$ Conclusion: Maximum pull-out torque occurs at a rotor speed of **1,414 rpm**. Distractor Analysis: - Option A: at breakdown slip s = 0.100 - Option B: at breakdown slip s = 0.215 (Correct) - Option C: at breakdown slip s = 0.306 - Option D: at breakdown slip s = 0.400
Problem 3
A three-phase electrical power network is modeled on a common base of $100.0\text{ MVA}$ and $115.0\text{ kV}$ in the transmission section: - Synchronous generator subtransient reactance: $X_d'' = 0.15\text{ pu}$ - Step-up power transformer leakage reactance: $X_T = 0.10\text{ pu}$ - Transmission line series reactance: $X_{line} = 0.15\text{ pu}$ A bolted three-phase symmetrical fault occurs at the remote receiving-end bus of the transmission line. Prefault voltage is nominal ($V_f = 1.00\text{ pu}$). What are the per-unit subtransient symmetrical fault current $I_f''$ and the corresponding three-phase short-circuit capacity $S_{sc}$?
- A1.25 pu (with S_sc = 125.0 MVA)
- B1.67 pu (with S_sc = 167.0 MVA)
- C2.50 pu (yielding short-circuit capacity S_sc = 250.0 MVA and I_f = 1.26 kA)correct
- D3.33 pu (with S_sc = 333.0 MVA)
Show the solution
**Step 1: Compute Total Thevenin Subtransient Reactance $X_{th}''$** From the FE Reference Handbook (Power Systems / Fault Analysis / Symmetrical Three-Phase Faults): Because all reactances are connected in series between the internal generator EMF and the fault location on a common base: $$X_{th}'' = X_d'' + X_T + X_{line} = 0.15\text{ pu} + 0.10\text{ pu} + 0.15\text{ pu} = 0.40\text{ pu}$$ **Step 2: Calculate Subtransient Fault Current $I_f''$ in Per Unit** $$I_f'' = \frac{V_f}{X_{th}''} = \frac{1.00\text{ pu}}{0.40\text{ pu}} = 2.50\text{ pu}$$ **Step 3: Calculate Short-Circuit Capacity $S_{sc}$** $$S_{sc} = \frac{S_{base}}{X_{th}''} = \frac{100.0\text{ MVA}}{0.40} = 250.0\text{ MVA}$$ **Step 4: Verify Base Current and Physical Current** $$I_{base} = \frac{S_{base}}{\sqrt{3} V_{base}} = \frac{100.0 \times 10^6\text{ VA}}{\sqrt{3}(115.0 \times 10^3\text{ V})} = 502.04\text{ A}$$ $$I_{f,actual}'' = 2.50 \times 502.04\text{ A} = 1{,}255.1\text{ A} = 1.255\text{ kA} \approx 1.26\text{ kA}$$ Conclusion: The fault current is **$2.50\text{ pu}$** yielding a short-circuit capacity of **$250.0\text{ MVA}$**. Distractor Analysis: - Option A: with S_sc = 125.0 MVA - Option B: with S_sc = 167.0 MVA - Option C: yielding short-circuit capacity S_sc = 250.0 MVA and I_f = 1.26 kA (Correct) - Option D: with S_sc = 333.0 MVA