An industrial AC voltage source $v(t) = 170.0\cos(377 t)\text{ V}$ ($V_{rms} = 120.0\text{ V rms}, \omega = 377\text{ rad/s}, f = 60.0\text{ Hz}$) powers a two-branch parallel network: - Branch 1 (inductive load): series resistor $R_1 = 12.0\ \Omega$ and inductor $L = 80.0\text{ mH} = 0.080\text{ H}$ ($X_L = \omega L = 30.16\ \Omega$) - Branch 2 (shunt power factor correction capacitor): capacitor $C = 55.0\ \mu\text{F}$ ($X_C = 1/(\omega C) = 48.23\ \Omega$) What are the total source current magnitude $|\mathbf{I}_{total}|$ and the overall power factor of the combined network?
- A3.70 A (uncompensated motor branch current)
- B1.66 A (with improved power factor pf = 0.822 lagging)correct
- C6.19 A (simple scalar addition of branch currents error)
- D0.83 A (half current error)
Show the solution
**Step 1: Compute Branch Impedances and Currents** From the FE Reference Handbook (Electrical and Computer Engineering / AC Circuits / Parallel Admittance): Supply reference phasor: $\mathbf{V} = 120.0\angle 0^\circ\text{ V rms}$. - Branch 1 (Inductive Branch): $$\mathbf{Z}_1 = R_1 + j X_L = 12.0 + j 30.16\ \Omega$$ $$|\mathbf{Z}_1| = \sqrt{12.0^2 + 30.16^2} = \sqrt{144.0 + 909.6} = 32.46\ \Omega$$ $$\theta_1 = \arctan\left(\frac{30.16}{12.0}\right) = 68.30^\circ$$ $$\mathbf{I}_1 = \frac{120.0\angle 0^\circ}{32.46\angle 68.30^\circ} = 3.697\angle -68.30^\circ\text{ A rms} = (1.367 - j 3.435)\text{ A}$$ - Branch 2 (Capacitor Branch): $$\mathbf{Z}_2 = -j X_C = -j 48.23\ \Omega$$ $$\mathbf{I}_2 = \frac{120.0\angle 0^\circ}{48.23\angle -90^\circ} = 2.488\angle +90^\circ\text{ A rms} = +j 2.488\text{ A}$$ **Step 2: Calculate Total Source Current Phasor** $$\mathbf{I}_{total} = \mathbf{I}_1 + \mathbf{I}_2 = 1.367 + j(-3.435 + 2.488) = (1.367 - j 0.947)\text{ A rms}$$ Magnitude of total current: $$|\mathbf{I}_{total}| = \sqrt{(1.367)^2 + (-0.947)^2} = \sqrt{1.8687 + 0.8968} = \sqrt{2.7655} = 1.663\text{ A rms} \approx 1.66\text{ A}$$ **Step 3: Calculate Power Factor** Active power: $P = V_{rms} \text{Re}\{\mathbf{I}^*\} = (120.0)(1.367) = 164.0\text{ W}$. Apparent power: $S = V_{rms} |\mathbf{I}_{total}| = (120.0)(1.663) = 199.56\text{ VA}$. $$\text{pf} = \frac{P}{S} = \frac{164.0}{199.56} = 0.8218 \approx 0.822\text{ lagging}$$ Conclusion: Total current is **$1.66\text{ A}$** with power factor **$0.822\text{ lagging}$**.