Electricity and Magnetism on the FE Mechanical exam

Electricity and Magnetism accounts for 6 of the 110 questions — 5.5% of your exam. It sits in the middle of the paper by weight: too big to skip, not big enough to dominate your plan.

Questions6
Share of exam5.5%
Rank by weight10/14
In our bank20

What Electricity and Magnetism covers

On the FE Mechanical exam this area covers charge, electric fields and potential, capacitance, current and resistance, DC and AC circuits, magnetic fields and induction, and inductance.

What the questions look like: A field or force, a capacitance or inductance, or a simple circuit computation.

Worth knowing cold: Treat this as physics rather than circuit design. The questions stay close to the fundamental definitions.

3 free Electricity and Magnetism practice problems

These come from our FE Mechanical bank, written to the same specification as the exam. Try each one before opening the solution.

Problem 1

A single-phase industrial induction motor operates from a $V_{\text{rms}} = 240\text{ V}, 60\text{ Hz}$ electrical supply. The motor draws an apparent power $S_1 = 6.00\text{ kVA}$ at a lagging power factor $\text{pf}_1 = 0.750$. A shunt power factor correction capacitor is to be connected in parallel with the motor terminals to increase the overall operating power factor to $\text{pf}_2 = 0.950$ lagging. The required capacitance $C$ of this parallel capacitor is most nearly:

  1. A74.2 μF
  2. B92.5 μF
  3. C115 μFcorrect
  4. D148 μF
Show the solution

Step 1: Calculate active power ($P$) and initial reactive power ($Q_1$) drawn by the motor: - Real (active) power: $$P = S_1 \cdot \text{pf}_1 = 6.00\text{ kVA} \times 0.750 = 4.50\text{ kW} = 4{,}500\text{ W}$$ - Initial phase angle: $$\theta_1 = \arccos(0.750) = 41.4096^\circ \implies \tan\theta_1 = \tan(41.4096^\circ) = 0.881917$$ - Initial reactive power: $$Q_1 = P \cdot \tan\theta_1 = 4{,}500\text{ W} \times 0.881917 = 3{,}968.6\text{ VAR}$$ Step 2: Determine target reactive power ($Q_2$) at $\text{pf}_2 = 0.950$ lagging: $$\theta_2 = \arccos(0.950) = 18.1949^\circ \implies \tan\theta_2 = \tan(18.1949^\circ) = 0.328684$$ $$Q_2 = P \cdot \tan\theta_2 = 4{,}500\text{ W} \times 0.328684 = 1{,}479.1\text{ VAR}$$ Step 3: Compute the required reactive power compensation supplied by the capacitor ($Q_C$): $$Q_C = Q_1 - Q_2 = 3{,}968.6\text{ VAR} - 1{,}479.1\text{ VAR} = 2{,}489.5\text{ VAR}$$ Step 4: Calculate the required shunt capacitance $C$: From the NCEES FE Reference Handbook (Electrical and Computer Engineering, AC Power): $$Q_C = \dfrac{V_{\text{rms}}^2}{X_C} = V_{\text{rms}}^2 \cdot (\omega C) \implies C = \dfrac{Q_C}{\omega \cdot V_{\text{rms}}^2}$$ where angular frequency is $\omega = 2\pi f = 2\pi (60\text{ Hz}) = 376.991\text{ rad/s}$ and $V_{\text{rms}}^2 = (240\text{ V})^2 = 57{,}600\text{ V}^2$. $$C = \dfrac{2{,}489.5\text{ VAR}}{376.991\text{ rad/s} \times 57{,}600\text{ V}^2} = \dfrac{2{,}489.5}{2.17147 \times 10^7} = 1.14646 \times 10^{-4}\text{ F} = 114.65\ \mu\text{F} \approx 115\ \mu\text{F}$$ Distractor Analysis: - Option A (74.2 μF) calculates capacitance corresponding to correcting power factor to 0.88 instead of 0.95. - Option B (92.5 μF) evaluates capacitance at $f = 50\text{ Hz}$ or divides by an extraneous line-to-line factor $\sqrt{3}$. - Option C (115 μF) is the exact required shunt power factor correction capacitance. - Option D (148 μF) calculates capacitor size for overcorrection or evaluates $Q_1$ alone without subtracting target $Q_2$.

Problem 2

A balanced three-phase, $60\text{ Hz}$, $480\text{ V}_{\text{rms}}$ (line-to-line) industrial facility draws a real power $P = 150\text{ kW}$ at an initial lagging power factor $\text{pf}_1 = 0.750$. Plant engineering installs a delta-connected three-phase capacitor bank across the incoming supply lines to correct the overall operating power factor to $\text{pf}_2 = 0.950$ lagging. According to three-phase AC power principles in the NCEES FE Reference Handbook, what capacitance $C$ per phase must each capacitor in the delta-connected bank possess?

  1. A$106\ \mu\text{F}$
  2. B$955\ \mu\text{F}$
  3. C$507\ \mu\text{F}$
  4. D$318\ \mu\text{F}$correct
Show the solution

From the NCEES FE Reference Handbook (Electrical and Computer Engineering — AC Power & Power Factor Correction): The real power absorbed by the facility is $P = 150\text{ kW}$. The initial phase angle is $\theta_1 = \arccos(0.750) = 41.4096^\circ$, and the uncorrected reactive power is: $Q_1 = P \tan\theta_1 = 150\text{ kW} \times \tan(41.4096^\circ) = 150 \times 0.881917 = 132.288\text{ kVAR}$. To reach target lagging power factor $\text{pf}_2 = 0.950$, the target phase angle is $\theta_2 = \arccos(0.950) = 18.1949^\circ$, giving target reactive power: $Q_2 = P \tan\theta_2 = 150\text{ kW} \times \tan(18.1949^\circ) = 150 \times 0.328684 = 49.303\text{ kVAR}$. The total three-phase capacitive reactive power required from the capacitor bank is: $Q_C = Q_1 - Q_2 = 132.288\text{ kVAR} - 49.303\text{ kVAR} = 82.985\text{ kVAR} = 82,985\text{ VAR}$. Because the capacitor bank is delta-connected across the $480\text{ V}$ lines, each phase capacitor branch experiences full line-to-line voltage $V_\Delta = V_L = 480\text{ V}_{\text{rms}}$ and provides one-third of total reactive power: $Q_{C,\text{phase}} = \frac{Q_C}{3} = \frac{82,985\text{ VAR}}{3} = 27,661.7\text{ VAR}$. The required capacitive reactance per branch is: $X_C = \frac{V_L^2}{Q_{C,\text{phase}}} = \frac{(480\text{ V})^2}{27,661.7\text{ VAR}} = \frac{230,400}{27,661.7} = 8.3292\ \Omega$. With line frequency $f = 60\text{ Hz}$, angular frequency is $\omega = 2\pi (60) = 376.991\text{ rad/s}$. The required delta capacitance per phase is: $C = \frac{1}{\omega X_C} = \frac{1}{376.991 \times 8.3292} = \frac{1}{3139.99} = 3.1847 \times 10^{-4}\text{ F} = 318.5\ \mu\text{F} \approx 318\ \mu\text{F}$. Distractor A ($106\ \mu\text{F}$) mistakenly divides by an extra factor of 3. Distractor B ($955\ \mu\text{F}$) mistakenly uses phase-to-neutral voltage $V_{LN} = 480/\sqrt{3} = 277\text{ V}$ as if delta capacitors saw line-to-neutral voltage (a 3x over-sizing error). Distractor C ($507\ \mu\text{F}$) sizes capacitors to eliminate all initial reactive power $Q_1$, ignoring the target $0.95$ power factor. The result confirms significant reduction in line current and utility demand charges. Distractor Analysis: - Option A: Divides line voltage by 3 instead of sqrt(3) to obtain phase voltage in wye configuration. - Option B: Omits power factor, calculating apparent power (kVA) rather than active power (kW). - Option C: Calculates single-phase power instead of multiplying by 3 for three-phase total. - Option D: Correct. Full-load motor line current is 38.5 A and total active power is 26.8 kW.

Problem 3

A series RLC circuit consists of a resistor $R = 20.0\text{ }\Omega$, an inductor $L = 50.0\text{ mH} = 0.0500\text{ H}$, and a capacitor $C = 20.0\text{ }\mu\text{F} = 2.00 \times 10^{-5}\text{ F}$ connected to an AC voltage source. In accordance with resonance equations from the NCEES FE Reference Handbook ($f_0 = \frac{1}{2\pi\sqrt{L C}}$, $Q = \frac{1}{R}\sqrt{\frac{L}{C}}$), the resonant frequency ($f_0$, in Hz) and quality factor ($Q$) of the series circuit are:

  1. A115.0 Hz, Q = 1.80
  2. B159.2 Hz, Q = 2.50correct
  3. C210.5 Hz, Q = 3.20
  4. D265.0 Hz, Q = 4.00
Show the solution

Step 1: Calculate the resonant angular frequency ($\omega_0$): $$\omega_0 = \frac{1}{\sqrt{L C}} = \frac{1}{\sqrt{(0.0500\text{ H})(2.00 \times 10^{-5}\text{ F})}} = \frac{1}{\sqrt{1.00 \times 10^{-6}}} = \frac{1}{1.00 \times 10^{-3}} = 1000.0\text{ rad/s}$$ Step 2: Determine resonant cyclic frequency ($f_0$): $$f_0 = \frac{\omega_0}{2\pi} = \frac{1000.0\text{ rad/s}}{2\pi} = 159.155\text{ Hz} = 159.2\text{ Hz}$$ Step 3: Calculate the circuit quality factor ($Q$): $$Q = \frac{\omega_0 L}{R} = \frac{(1000.0\text{ rad/s})(0.0500\text{ H})}{20.0\text{ }\Omega} = \frac{50.0}{20.0} = 2.500 = 2.50$$ $$\text{Alternatively: } Q = \frac{1}{R} \sqrt{\frac{L}{C}} = \frac{1}{20.0} \sqrt{\frac{0.0500}{2.00 \times 10^{-5}}} = \frac{1}{20.0} \sqrt{2500} = \frac{50.0}{20.0} = 2.50$$ Distractor Analysis: - Option A: Uses parallel RLC quality factor formula ($Q = R \sqrt{C/L} = 0.40$ scaled). - Option B: Correct. - Option C: Uses angular frequency in place of cyclic frequency. - Option D: Omits square root in resonant calculation.

Find out where you actually stand

A free 20-question diagnostic across every FE Mechanical knowledge area, scored in the real exam interface. You get a projected score and the areas costing you the most — so you know whether Electricity and Magnetism is where your time should go at all.

Start the free Mechanical diagnostic

Retaking the FE Mechanical exam?

Copy the scores from your NCEES diagnostic report and see whether Electricity and Magnetism is where your next attempt gains the most points, or whether another area deserves the time first.

Analyze my diagnostic report

Other FE Mechanical knowledge areas