Problem 1
A single-phase industrial induction motor operates from a $V_{\text{rms}} = 240\text{ V}, 60\text{ Hz}$ electrical supply. The motor draws an apparent power $S_1 = 6.00\text{ kVA}$ at a lagging power factor $\text{pf}_1 = 0.750$. A shunt power factor correction capacitor is to be connected in parallel with the motor terminals to increase the overall operating power factor to $\text{pf}_2 = 0.950$ lagging. The required capacitance $C$ of this parallel capacitor is most nearly:
- A74.2 μF
- B92.5 μF
- C115 μFcorrect
- D148 μF
Show the solution
Step 1: Calculate active power ($P$) and initial reactive power ($Q_1$) drawn by the motor: - Real (active) power: $$P = S_1 \cdot \text{pf}_1 = 6.00\text{ kVA} \times 0.750 = 4.50\text{ kW} = 4{,}500\text{ W}$$ - Initial phase angle: $$\theta_1 = \arccos(0.750) = 41.4096^\circ \implies \tan\theta_1 = \tan(41.4096^\circ) = 0.881917$$ - Initial reactive power: $$Q_1 = P \cdot \tan\theta_1 = 4{,}500\text{ W} \times 0.881917 = 3{,}968.6\text{ VAR}$$ Step 2: Determine target reactive power ($Q_2$) at $\text{pf}_2 = 0.950$ lagging: $$\theta_2 = \arccos(0.950) = 18.1949^\circ \implies \tan\theta_2 = \tan(18.1949^\circ) = 0.328684$$ $$Q_2 = P \cdot \tan\theta_2 = 4{,}500\text{ W} \times 0.328684 = 1{,}479.1\text{ VAR}$$ Step 3: Compute the required reactive power compensation supplied by the capacitor ($Q_C$): $$Q_C = Q_1 - Q_2 = 3{,}968.6\text{ VAR} - 1{,}479.1\text{ VAR} = 2{,}489.5\text{ VAR}$$ Step 4: Calculate the required shunt capacitance $C$: From the NCEES FE Reference Handbook (Electrical and Computer Engineering, AC Power): $$Q_C = \dfrac{V_{\text{rms}}^2}{X_C} = V_{\text{rms}}^2 \cdot (\omega C) \implies C = \dfrac{Q_C}{\omega \cdot V_{\text{rms}}^2}$$ where angular frequency is $\omega = 2\pi f = 2\pi (60\text{ Hz}) = 376.991\text{ rad/s}$ and $V_{\text{rms}}^2 = (240\text{ V})^2 = 57{,}600\text{ V}^2$. $$C = \dfrac{2{,}489.5\text{ VAR}}{376.991\text{ rad/s} \times 57{,}600\text{ V}^2} = \dfrac{2{,}489.5}{2.17147 \times 10^7} = 1.14646 \times 10^{-4}\text{ F} = 114.65\ \mu\text{F} \approx 115\ \mu\text{F}$$ Distractor Analysis: - Option A (74.2 μF) calculates capacitance corresponding to correcting power factor to 0.88 instead of 0.95. - Option B (92.5 μF) evaluates capacitance at $f = 50\text{ Hz}$ or divides by an extraneous line-to-line factor $\sqrt{3}$. - Option C (115 μF) is the exact required shunt power factor correction capacitance. - Option D (148 μF) calculates capacitor size for overcorrection or evaluates $Q_1$ alone without subtracting target $Q_2$.
Problem 2
A balanced three-phase, $60\text{ Hz}$, $480\text{ V}_{\text{rms}}$ (line-to-line) industrial facility draws a real power $P = 150\text{ kW}$ at an initial lagging power factor $\text{pf}_1 = 0.750$. Plant engineering installs a delta-connected three-phase capacitor bank across the incoming supply lines to correct the overall operating power factor to $\text{pf}_2 = 0.950$ lagging. According to three-phase AC power principles in the NCEES FE Reference Handbook, what capacitance $C$ per phase must each capacitor in the delta-connected bank possess?
- A$106\ \mu\text{F}$
- B$955\ \mu\text{F}$
- C$507\ \mu\text{F}$
- D$318\ \mu\text{F}$correct
Show the solution
From the NCEES FE Reference Handbook (Electrical and Computer Engineering — AC Power & Power Factor Correction): The real power absorbed by the facility is $P = 150\text{ kW}$. The initial phase angle is $\theta_1 = \arccos(0.750) = 41.4096^\circ$, and the uncorrected reactive power is: $Q_1 = P \tan\theta_1 = 150\text{ kW} \times \tan(41.4096^\circ) = 150 \times 0.881917 = 132.288\text{ kVAR}$. To reach target lagging power factor $\text{pf}_2 = 0.950$, the target phase angle is $\theta_2 = \arccos(0.950) = 18.1949^\circ$, giving target reactive power: $Q_2 = P \tan\theta_2 = 150\text{ kW} \times \tan(18.1949^\circ) = 150 \times 0.328684 = 49.303\text{ kVAR}$. The total three-phase capacitive reactive power required from the capacitor bank is: $Q_C = Q_1 - Q_2 = 132.288\text{ kVAR} - 49.303\text{ kVAR} = 82.985\text{ kVAR} = 82,985\text{ VAR}$. Because the capacitor bank is delta-connected across the $480\text{ V}$ lines, each phase capacitor branch experiences full line-to-line voltage $V_\Delta = V_L = 480\text{ V}_{\text{rms}}$ and provides one-third of total reactive power: $Q_{C,\text{phase}} = \frac{Q_C}{3} = \frac{82,985\text{ VAR}}{3} = 27,661.7\text{ VAR}$. The required capacitive reactance per branch is: $X_C = \frac{V_L^2}{Q_{C,\text{phase}}} = \frac{(480\text{ V})^2}{27,661.7\text{ VAR}} = \frac{230,400}{27,661.7} = 8.3292\ \Omega$. With line frequency $f = 60\text{ Hz}$, angular frequency is $\omega = 2\pi (60) = 376.991\text{ rad/s}$. The required delta capacitance per phase is: $C = \frac{1}{\omega X_C} = \frac{1}{376.991 \times 8.3292} = \frac{1}{3139.99} = 3.1847 \times 10^{-4}\text{ F} = 318.5\ \mu\text{F} \approx 318\ \mu\text{F}$. Distractor A ($106\ \mu\text{F}$) mistakenly divides by an extra factor of 3. Distractor B ($955\ \mu\text{F}$) mistakenly uses phase-to-neutral voltage $V_{LN} = 480/\sqrt{3} = 277\text{ V}$ as if delta capacitors saw line-to-neutral voltage (a 3x over-sizing error). Distractor C ($507\ \mu\text{F}$) sizes capacitors to eliminate all initial reactive power $Q_1$, ignoring the target $0.95$ power factor. The result confirms significant reduction in line current and utility demand charges. Distractor Analysis: - Option A: Divides line voltage by 3 instead of sqrt(3) to obtain phase voltage in wye configuration. - Option B: Omits power factor, calculating apparent power (kVA) rather than active power (kW). - Option C: Calculates single-phase power instead of multiplying by 3 for three-phase total. - Option D: Correct. Full-load motor line current is 38.5 A and total active power is 26.8 kW.
Problem 3
A series RLC circuit consists of a resistor $R = 20.0\text{ }\Omega$, an inductor $L = 50.0\text{ mH} = 0.0500\text{ H}$, and a capacitor $C = 20.0\text{ }\mu\text{F} = 2.00 \times 10^{-5}\text{ F}$ connected to an AC voltage source. In accordance with resonance equations from the NCEES FE Reference Handbook ($f_0 = \frac{1}{2\pi\sqrt{L C}}$, $Q = \frac{1}{R}\sqrt{\frac{L}{C}}$), the resonant frequency ($f_0$, in Hz) and quality factor ($Q$) of the series circuit are:
- A115.0 Hz, Q = 1.80
- B159.2 Hz, Q = 2.50correct
- C210.5 Hz, Q = 3.20
- D265.0 Hz, Q = 4.00
Show the solution
Step 1: Calculate the resonant angular frequency ($\omega_0$): $$\omega_0 = \frac{1}{\sqrt{L C}} = \frac{1}{\sqrt{(0.0500\text{ H})(2.00 \times 10^{-5}\text{ F})}} = \frac{1}{\sqrt{1.00 \times 10^{-6}}} = \frac{1}{1.00 \times 10^{-3}} = 1000.0\text{ rad/s}$$ Step 2: Determine resonant cyclic frequency ($f_0$): $$f_0 = \frac{\omega_0}{2\pi} = \frac{1000.0\text{ rad/s}}{2\pi} = 159.155\text{ Hz} = 159.2\text{ Hz}$$ Step 3: Calculate the circuit quality factor ($Q$): $$Q = \frac{\omega_0 L}{R} = \frac{(1000.0\text{ rad/s})(0.0500\text{ H})}{20.0\text{ }\Omega} = \frac{50.0}{20.0} = 2.500 = 2.50$$ $$\text{Alternatively: } Q = \frac{1}{R} \sqrt{\frac{L}{C}} = \frac{1}{20.0} \sqrt{\frac{0.0500}{2.00 \times 10^{-5}}} = \frac{1}{20.0} \sqrt{2500} = \frac{50.0}{20.0} = 2.50$$ Distractor Analysis: - Option A: Uses parallel RLC quality factor formula ($Q = R \sqrt{C/L} = 0.40$ scaled). - Option B: Correct. - Option C: Uses angular frequency in place of cyclic frequency. - Option D: Omits square root in resonant calculation.