A commercial refrigeration unit operates on a standard vapor-compression refrigeration cycle using refrigerant R-134a. As shown on the pressure-enthalpy (P-h) diagram, saturated vapor enters the compressor at State 1 ($P_1 = 201\text{ kPa}$, $h_1 = 244.5\text{ kJ/kg}$) and is compressed to superheated vapor at State 2 ($P_2 = 1.00\text{ MPa}$, $h_2 = 282.7\text{ kJ/kg}$). The refrigerant leaves the condenser as saturated liquid at State 3 ($P_3 = 1.00\text{ MPa}$, $h_3 = 107.3\text{ kJ/kg}$) and throttles isenthalpically across an expansion valve to State 4 ($h_4 = h_3$). If the evaporator produces a cooling capacity of $\dot{Q}_L = 35.0\text{ kW}$, the Coefficient of Performance (COP) of the cycle is most nearly:
- A2.74
- B3.59correct
- C4.25
- D5.12
Show the solution
Step 1: Calculate the specific refrigeration effect in the evaporator: $$q_L = h_1 - h_4 = 244.5\text{ kJ/kg} - 107.3\text{ kJ/kg} = 137.2\text{ kJ/kg}$$ Step 2: Calculate the specific work required by the compressor: $$w_c = h_2 - h_1 = 282.7\text{ kJ/kg} - 244.5\text{ kJ/kg} = 38.2\text{ kJ/kg}$$ Step 3: Calculate the Coefficient of Performance (COP): $$COP = \dfrac{\text{Desired Output}}{\text{Required Work Input}} = \dfrac{q_L}{w_c} = \dfrac{137.2\text{ kJ/kg}}{38.2\text{ kJ/kg}} = 3.5916 \approx 3.59$$ Step 4: Verify compressor power input and mass flow rate: $$\dot{m} = \dfrac{\dot{Q}_L}{q_L} = \dfrac{35.0\text{ kW}}{137.2\text{ kJ/kg}} = 0.2551\text{ kg/s}$$ $$\dot{W}_c = \dot{m} w_c = 0.2551 \times 38.2 = 9.745\text{ kW}$$ $$COP = \dfrac{35.0}{9.745} = 3.59$$ Distractor Analysis: - Option A (2.74) calculates heat pump COP minus 1 using condenser heat duty in the denominator. - Option C (4.25) uses an ideal Carnot COP between saturation temperatures without considering superheat. - Option D (5.12) neglects the expansion valve throttling irreversibility, using isentropic expansion.